Skip to Content

Distribution cabinet - With ATS 800A (1850A—850A—650 mm)

https://www.nanwan.cc/web/image/product.template/2621/image_1920?unique=d7eea39
(0 review)

$ 9,337.83 9337.83 USD Tax Excluded

9,337.83 Bs Tax Excluded

Not Available For Sale

  • Electrical
  • Transfer
  • Dimensions

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days

ENCLOSURE DISTRIBUTION CON ATS 800A (1850×850×650 mm) switches the load between mains and generator: it monitors the mains, commands the start, transfers, and re-transfers with a delay so the set is not shocked.

In contactor-based ATS the wear is in the main contacts and the mechanical interlock. In motorised-breaker ATS it is the charging motor and the limit switches. Knowing which one your panel uses tells you what to keep in stock.

Specifications and compatibility

Electrical type
Distribution Cabinet / Distribution Board
Dimensions
184 x 83 x 65 cm

How to verify before ordering

  • Match the number of poles, the rated current and the switching type (contactor or motorised breaker).
  • Check the ATS control voltage: 110 V, 220 V or 24 V depending on the panel it goes into.
  • Confirm whether neutral is switched. On installations with a distributed neutral this is mandatory.

Frequently asked questions

The set starts but the load is not transferred. What do I check?

The signal first: mains-sensing relay, control fuse and the wiring between ATS and set. Then the interlock: if the mains contactor does not release, the generator contactor will not close, by design.

Can I fit an ATS of another brand?

Yes, as long as control voltage and logic are compatible with the set panel. With a controller-based set, the ATS must accept that controller transfer signal.

Related parts

See the spare parts catalogue or request a quotation quoting the equipment reference. Third-party trademarks are cited for identification purposes only.

Specifications

Characteristics
Dimensions 184 x 83 x 65 cm
Electrical power
Electrical Distribution cabinet
Others
Transfer 800A